Hi-FLEXI C Series

Hi-FLEXI C Series HP 8HP 10HP
Model Power Supply AC3Φ380~450V/50Hz AVW-76UESR AVW-96UESR
AC3Φ380V/60Hz AVW-76U7SR AVW-96U7SR
AC3Φ220V/60Hz AVW-76U9SR AVW-96U9SR
Cooling Capacity Kw 22.4 28.0
kBtu/h 76.5 95.6
Consumption Power KW 6.3 8.3
EER 3.6 3.4
Heating Capacity KW 25.0 31.5
kBtu/h 85.3 107.5
Consumption Power KW 5.9 7.8
COP 4.2 4.0
Air Flow Rate m³/h 7260 9000
Outer Dimension(H×W×D) mm 1650×1100×390
Packing Dimension(H×W×D) mm 1748×1151×500
Net Weight kg 168 168
Gross Weight kg 179 179
Compressor Quantity 1 1
Condenser Fan Quantity 2 2
Gas Line mm Ф19.05 Ф22.2
Liquid Line mm Ф9.53 Ф12.7
Max. number of connectable IDU 10 10
Max. Piping Length m 100 100
Height Difference Between OUT&IDU m 50(40) 50(40)
Between IDUS m 15 15
Noise Level (Cooling/Heating*2) dB(A) 53/55 56/58
Operation Range Cooling ℃ DB          -5~48
Heating ℃ WB          -20~15
Note: For connection with ” * ” please contact with our technical engineer.

 

NOTES:
1.The nominal cooling and heating capacities show the capacities when the outdoor with the 100% rating of indoor unit.
Cooling Operation Conditions
Indoor Air Inlet Temperature:27℃DB/19℃WB
Outdoor Air Inlet Temperature:35℃DB
Piping Length:7.5Meters Piping Lift:0 Meter
2.The sound pressure level is based on following conditions:
1.5 Meters from floor Level,and 1Meter from the unit service cover surface.
The above data was measured in an anechoic chamber so that reflected sounde shoudle be taken into consideration in the field.